Anonymized manufacturing case study

A pharmaceutical cooling plant improved reported average COP from 4.75 to 5.41.

This page preserves the report detail: equipment brands and sizes, BAS compatibility, control bands, daily COP and weather data, redrawn frequency charts, and the published COP-uplift calculation.

Published COP uplift
12.11%

Published by the source report for the AI operating period.

AI operating window
37 days

Sep 1 to Oct 7 AI control compared with Jun 1 to Jul 7 autonomous control.

Average COP
4.75 -> 5.41

Baseline average to AI-period average.

Plant inventory

Equipment brands, capacities, and active plant topology

The report describes a secondary-pump variable-flow chilled-water system. The central plant includes four chillers with one standby unit, four chilled-water pumps, four condenser-water pumps, three air-side chilled-water pumps, and four process-side chilled-water pumps. Normal operation is one chiller paired with one pump.

EquipmentBrandSpecificationStatus
Centrifugal chillerTraneCooling capacity 650RT / Power 402kWRunning
Chilled-water pumpGrundfosHead 20m / Power 30kW / Flow 350m3/hRunning
Condenser-water pumpXylemHead 22m / Power 45kW / Flow 190m3/hRunning
Cooling towerBACFlow 500m3/h / Power 22kWRunning

Control and BAS compatibility

The AI layer stayed compatible with existing group control.

The platform supports one-click switching between existing group control and AI control. Operators can also apply AI recommendations to group-control setpoints for condenser-water pump frequency and cooling-tower frequency.

Condenser-water pump band
42Hz to 50Hz, constrained by low-flow protection.
Cooling-tower fan band
22Hz to 50Hz, optimized against plant energy and indoor-temperature response.
Current optimization scope
Condenser-water pumps and cooling towers.
Reserved future interfaces
Chilled-water supply temperature and chilled-water pump frequency.
Data source
BAS operating records, daily system COP, outdoor dry-bulb temperature, and outdoor wet-bulb temperature.

Redrawn Figure 2

Cooling-water pump and cooling-tower optimization loop

The source report frames the control as reinforcement learning: read operating state, check load and action limits, update strategy, and execute pump/tower actions.

  • The reward combines overall operating energy and indoor-temperature change.
  • The strategy directly targets condenser-side energy instead of controlling only an intermediate temperature-difference variable.
  1. 01

    Optimization cycle starts

  2. 02

    Read state parameters

  3. 03

    Load above start threshold?

  4. 04

    State parameters inside allowed action range?

  5. 05

    Discretize state parameters

  6. 06

    Update Q(s,a) with reward feedback

  7. 07

    Use epsilon-greedy strategy for pump/tower command

  8. 08

    Execute action

  9. 09

    Optimization cycle ends

Jul 2 baseline condenser-water pump frequency

Redrawn from the source figure: fixed-frequency operation around 48Hz, 47.6Hz, and 45.4Hz.

494746454400:0003:0006:0009:0012:0015:0018:0021:0023:45
CwPump #1CwPump #2CwPump #4

Source chart shows stable fixed operation rather than active search.

Sep 28 AI condenser-water pump frequency

Redrawn from the source figure: two running pumps moved within the 42Hz-50Hz control band.

524946434000:0003:0006:0009:0010:3012:3015:0018:0021:0023:55
CwPump #1CwPump #3

The AI period includes deliberate drops near mid-day and late evening, then returns to higher frequency when conditions require it.

Jul 2 baseline cooling-tower fan frequency

Redrawn from the source figure: tower fans held near fixed frequency levels.

554943363000:0003:0006:0009:0012:0015:0018:0021:0023:35
Tower #1Tower #2Tower #3Tower #4

The baseline chart is nearly flat, with one visible transient dip.

Sep 28 AI cooling-tower fan frequency

Redrawn from the source figure: tower fans stepped down and up across the day.

514743393500:0003:0006:0009:0011:3014:0017:0019:3022:3023:55
Tower #4Tower #1Tower #3

The report text states AI tower operation reduced tower running energy by about 30%.

Calculation detail

COP uplift and operating-period calculation

  1. 1. Delta COP = AI average COP - baseline average COP = 5.41 - 4.75 = 0.66.
  2. 2. Published report uplift = 12.11%.
  3. 3. Displayed rounded averages reproduce approximately (5.41 - 4.75) / 5.41 = 12.2%; this page keeps the report's published 12.11% value.
  4. 4. The report's savings formula is: energy saved = AI-period total energy * COP uplift / (1 - COP uplift).
Baseline period
Jun 1 to Jul 7 autonomous-control operation; 27 valid daily records after missing-power-data exclusions.
Baseline averages
COP 4.75, outdoor dry-bulb 22.66C, outdoor wet-bulb 19.36C.
AI period
Sep 1 to Oct 7 AI control; 37 daily records.
AI averages
COP 5.41, outdoor dry-bulb 25.64C, outdoor wet-bulb 22.43C.
AI-period minimum COP
4.84, from the daily appendix table.

Redrawn Figure 7

High-efficiency cooling-plant benchmark table

The source report compares the AI-period average COP of 5.41 with this benchmark table and states that the result has exceeded the level-2 high-efficiency plant threshold and is close to level 1.

ClimateLevel 3Level 2Level 1
Severe cold>=4.2>=4.6>=5.3
Cold>=4.2>=4.6>=5.3
Hot summer, cold winter>=4.6>=5.1>=5.5
Hot summer, warm winter>=4.7>=5.2>=5.5
Temperate>=4.2>=4.7>=5.3

Appendix data and redrawn Figures 8-9

Daily COP, dry-bulb, and wet-bulb records used for the scatter plots

All daily points extracted by MarkItDown from the report appendix are preserved below, and the two COP-weather scatter plots are redrawn from these points.

COP vs wet-bulb temperature

29262219154.04.55.05.56.0COP
Autonomous controlAI control

COP vs outdoor dry-bulb temperature

33292521174.04.55.05.56.0COP
Autonomous controlAI control
ModeDateCOPDry-bulb CWet-bulb C
Autonomous controlJun 14.9521.2718.27
Autonomous controlJun 24.7922.4617.78
Autonomous controlJun 35.2220.3615.11
Autonomous controlJun 85.1221.2917.67
Autonomous controlJun 95.0023.2318.43
Autonomous controlJun 104.9523.0617.79
Autonomous controlJun 115.0921.2417.54
Autonomous controlJun 145.0720.8017.49
Autonomous controlJun 155.1121.5716.96
Autonomous controlJun 165.1420.7116.87
Autonomous controlJun 175.0718.2517.24
Autonomous controlJun 184.8519.3018.77
Autonomous controlJun 194.6120.5219.80
Autonomous controlJun 204.5722.3119.73
Autonomous controlJun 214.7123.5818.96
Autonomous controlJun 224.8722.6917.77
Autonomous controlJun 235.0620.2417.18
Autonomous controlJun 244.9418.1117.63
Autonomous controlJun 254.6421.1719.72
Autonomous controlJun 264.6021.6219.60
Autonomous controlJul 14.4523.8620.88
Autonomous controlJul 24.3024.2721.66
Autonomous controlJul 34.2824.6721.84
Autonomous controlJul 44.3126.1221.82
Autonomous controlJul 54.3425.1121.78
Autonomous controlJul 64.1431.3927.41
Autonomous controlJul 74.1432.5426.95
AI controlSep 15.4826.1021.77
AI controlSep 25.5527.0622.70
AI controlSep 35.4926.9623.74
AI controlSep 45.2728.6925.27
AI controlSep 55.0328.1825.15
AI controlSep 65.2228.7124.63
AI controlSep 75.4828.1524.29
AI controlSep 85.5928.1723.43
AI controlSep 95.6227.5722.85
AI controlSep 105.6727.7822.56
AI controlSep 115.5228.8024.47
AI controlSep 125.2827.4824.90
AI controlSep 135.3425.5023.95
AI controlSep 145.5524.6523.29
AI controlSep 155.5624.4223.51
AI controlSep 165.4425.3023.86
AI controlSep 175.4427.7323.87
AI controlSep 185.1129.2425.74
AI controlSep 194.8830.1926.60
AI controlSep 205.1326.8624.41
AI controlSep 215.5423.2020.68
AI controlSep 225.7621.0419.38
AI controlSep 235.7120.4218.89
AI controlSep 245.5323.1122.05
AI controlSep 255.3826.6323.95
AI controlSep 265.3025.6323.42
AI controlSep 274.9127.6224.71
AI controlSep 284.8825.8024.58
AI controlSep 294.8427.4024.55
AI controlSep 304.9424.1522.09
AI controlOct 15.2323.6219.32
AI controlOct 25.9822.9517.60
AI controlOct 35.6822.6318.51
AI controlOct 45.3323.5418.88
AI controlOct 55.8122.2616.79
AI controlOct 65.8321.4516.93
AI controlOct 75.8119.5516.60

Run the same measurement discipline on your cooling plant.

We can review BAS points, operating history, equipment sizes, and metering coverage to determine whether a similar AI supervisory layer is practical.